Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Migration of unmigrated content due to installation of a new plugin

Q649. Do we include the quantity of SF6 contained in hermetically sealed equipment when determining applicability under subpart DD?

 

A649. No, hermetically sealed-pressure equipment is excluded when determining if you exceed the reporting threshold of 17,820 pounds according to 98.301(a). However, the calculation parameters specified in equation DD-1 do include the quantity of SF6 contained in hermetically sealed equipment, so information on hermitically sealed equipment is included in the reporting requirements for subpart DD.

 

Wiki Markup
{show-to:group=confluence-Users}{_}Footer / References Bar which is Visible to the public{_}{show-to}

Panel

Updated on

Page info
modified-date
modified-date
dateformatdd/MM/YY HH:mm

Wiki Markup
{show-to:group=confluence-Users}
{info}
Source: EPA (David Jacobson, 3/20/2012)

Approval / Publishing History: Version 1, minor revisions per S. Bogle 3/1/18

Expiration: none

Relevant Subpart: DD
{info}{_}History Panel For Internal Use - Not Visible to the Public{_}{show-to}

This web site is maintained by a contractor to the U.S. Environmental Protection Agency (RY2021.R.02)