Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Migration of unmigrated content due to installation of a new plugin
longname
Q649. Hermetic seals should not leak. Do we include the quantity of SF6 contained in hermetically sealed equipment when determining applicability under subpart DD? 

A649. No, hermetically sealed-pressure equipment is excluded when determining if you exceed the reporting threshold of 17,820 pounds according to 98.301(a). However, the calculation parameters specified in equation DD-1 do include the quantity of SF6 contained in hermetically sealed equipment, so information on hermitically sealed equipment is included in the reporting requirements for subpart DD.

Wiki Markup
{show-to:group=confluence-Users}{center}{_}Footer / References Bar which is Visible to the public{_}{center}{show-to}

Panel

Updated on

Page info
modified-date
modified-date
dateformatdd/MM/YY HH:mm

Wiki Markup
{show-to:group=confluence-Users}
{info}
Source: EPA (David Jacobson, 3/20/2012)

Approval / Publishing History: Version 1

Expiration : none

Relevant Subpart: DD
{info}{center}{_}History Panel For Internal Use - Not Visible to the Public{_}{center}{show-to}

This web site is maintained by a contractor to the U.S. Environmental Protection Agency (RY2021.R.02)