Q649.

...

Hermetic

...

seals

...

should

...

not

...

leak.

...

Do

...

we

...

include

...

the

...

quantity

...

of

...

SF6

...

contained

...

in

...

hermetically

...

sealed

...

equipment

...

when

...

determining

...

applicability

...

under

...

subpart

...

DD?

...

 

A649. No, hermetically sealed-pressure equipment is excluded when determining if you exceed the reporting threshold of 17,820 pounds according to 98.301(a). However, the calculation parameters specified in equation DD-1 do include the quantity of SF6 contained in hermetically sealed equipment, so information on hermitically sealed equipment is included in the reporting requirements for subpart DD.